Chiller always requests full condenser flow regardless of flow mode or pump type #7111

Open
1 of 3 tasks
mjwitte opened this issue Dec 26, 2018 · 4 comments · May be fixed by #10511
Open
1 of 3 tasks

Chiller always requests full condenser flow regardless of flow mode or pump type #7111

mjwitte opened this issue Dec 26, 2018 · 4 comments · May be fixed by #10511
Assignees
Labels
NewFeatureRequest This "issue" is a new feature request, not a defect report

Comments

@mjwitte
Copy link
Contributor

mjwitte commented Dec 26, 2018

Issue overview

User file with Chiller:Electric:EIR always requests full condenser flow rate, regardless of chiller flow mode, with variable speed towers and variable speed condenser pump.
Should this happen?
If so, should there be an additional flow mode to allow variable flow condenser?

Details

Some additional details for this issue (if relevant):

Checklist

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Defect file added EnergyPlusDevSuppor\DefectFiles\7000s\7111
  • Ticket added to Pivotal for defect (development team task)
  • Pull request created (the pull request will have additional tasks related to reviewing changes that fix this defect)
@mjwitte
Copy link
Contributor Author

mjwitte commented Jul 27, 2020

Certainly looks like this should be an option. How to control it is another question. Here's one article about that:
https://www.csemag.com/articles/control-sequences-for-chilled-water-systems/

@mjwitte mjwitte added the NewFeatureRequest This "issue" is a new feature request, not a defect report label Jul 27, 2020
@dmitry-ivanov-mm
Copy link

Hi there,

Is there a way to raise the priority of this issue? It hasn't been addressed since 2018 and makes results for the variable-speed condenser loop very inaccurate. At the same time variable-speed condenser loops are very common design.

Just trying to attract attention to this issue :)

Cheers

@giorgiolupato
Copy link

giorgiolupato commented Feb 22, 2022

Hi there,

Is there a way to raise the priority of this issue? It hasn't been addressed since 2018 and makes results for the variable-speed condenser loop very inaccurate. At the same time variable-speed condenser loops are very common design.

Just trying to attract attention to this issue :)

Cheers

Hi, unfortunately this is not a complete solution, but it can be a workaround (it's not perfect at all).

https://unmethours.com/question/40084/condenser-water-flow-rate-with-ems-energyplus/

@keigo-nomura
Copy link

keigo-nomura commented Jul 14, 2022

Still unresolved?

This is a problem not only when using cooling towers, but also when using seawater cooling by PlantComponent:TemperatureSource. Unlike cooling towers, it is not possible to make a compromise of variable tower fans instead of variable condenser water.

Or variable condenser flow is possible with any other chiller objects?

Hope this issue won't be left unattended forever.

@mjwitte mjwitte self-assigned this Mar 6, 2023
@lymereJ lymereJ assigned lymereJ and unassigned mjwitte May 9, 2024
@lymereJ lymereJ linked a pull request May 17, 2024 that will close this issue